NEC CodeFebruary 3, 2025• 11 min read

Transformer Sizing Guide: kVA Calculations & NEC Requirements

Proper transformer sizing ensures reliable power distribution. Learn kVA calculations and NEC Article 450 protection requirements.

PRIMARY480VSECONDARY208V75 kVA

Understanding kVA Ratings

Transformers are rated in kilovolt-amperes (kVA), representing their apparent power capacity. Unlike resistive loads measured in kW, kVA accounts for both real and reactive power.

kVA = (Volts × Amps) / 1000

Single-phase: kVA = (V × I) / 1000

Three-phase: kVA = (V × I × 1.732) / 1000

Sizing Steps

  1. Calculate total connected load — Sum all loads on the secondary
  2. Apply demand factors — Not all loads operate simultaneously
  3. Add growth allowance — Typically 20-25% for future expansion
  4. Select standard size — Choose next larger standard kVA rating

Standard Transformer Sizes

Common dry-type transformer ratings (kVA):

36915304575112.515022530050075010001500

Primary & Secondary Current

Once you know the kVA rating, calculate the full-load currents for conductor and protection sizing:

Single-Phase

I = kVA × 1000 / V

Three-Phase

I = kVA × 1000 / (V × 1.732)

Example: 75 kVA, 480V to 208V, 3-Phase

Primary current: 75,000 / (480 × 1.732) = 90.2A

Secondary current: 75,000 / (208 × 1.732) = 208.2A

Ampora — The Electrician's AI Companion

Instant NEC code answers, electrical calculators, and AI troubleshooting. Free on iOS.

Download Free

Overcurrent Protection (NEC 450.3)

NEC Article 450 provides specific requirements for transformer overcurrent protection. Rules differ based on voltage and transformer type.

PRIMARYOCPD125%TSECONDARYOCPD125%≤1000VNEC 450.3(B) - Dry-Type Transformers

Transformers 1000V or Less (450.3(B))

Protection MethodPrimary OnlyPrimary + Secondary
Primary OCPD (9A or more)125%250%
Primary OCPD (less than 9A)167%300%
Secondary OCPD125%

Conductor Sizing

Size conductors based on the full-load current at each voltage level:

  • Primary conductors: Sized for primary full-load current
  • Secondary conductors: Sized for secondary full-load current
  • Apply ampacity correction factors for temperature and conduit fill

Example Installation

Size a transformer for 150A of 208V, 3-phase load

1. Calculate required kVA:

kVA = (208 × 150 × 1.732) / 1000 = 54 kVA

2. Add 25% growth: 54 × 1.25 = 67.5 kVA

3. Select standard size: 75 kVA transformer

4. Primary current (480V): 90.2A

5. Primary OCPD (125%): 90.2 × 1.25 = 112.75A → 110A breaker

6. Primary conductors: #2 AWG copper (115A @ 75°C)

Installation Considerations

  • Ventilation: Dry-type transformers require adequate airflow
  • Clearances: Maintain manufacturer-specified clearances
  • Grounding: Secondary must be grounded per NEC 250
  • Accessibility: Ensure access for maintenance and inspection
★ Free on the App Store

Your Electrical Reference, Powered by AI

Join thousands of electricians using Ampora for instant NEC code answers, electrical calculations, and AI-powered troubleshooting — right from your phone.