Wire Types8 min readJanuary 25, 2025

THHN vs THWN Wire: What's the Difference?

Both are common building wire types, but they're rated for different conditions. Here's what electricians need to know about choosing the right wire.

THHN90°C DryNOT wet ratedVSTHWN-290°C Dry & WetWet location OKMost wire is dual-rated THHN/THWN-2

Decoding Wire Names

Wire designation letters tell you exactly what you're getting. Here's what each letter means:

THHN Breakdown

  • T - Thermoplastic insulation
  • H - Heat resistant (75°C)
  • H - High heat resistant (90°C)
  • N - Nylon jacket (abrasion resistant)

THWN Breakdown

  • T - Thermoplastic insulation
  • H - Heat resistant (75°C)
  • W - Wet location rated
  • N - Nylon jacket (abrasion resistant)

Quick Comparison

FeatureTHHNTHWNTHWN-2
Dry Location Rating90°C75°C90°C
Wet Location RatingNot rated75°C90°C
Wet Location UseNoYesYes
Conduit UseYesYesYes
Nylon JacketYesYesYes

The Real-World Answer: THHN/THWN-2

Here's what most electricians should know: modern wire is typically dual-rated THHN/THWN-2. Look at the wire jacket - you'll usually see both designations printed.

Dual-Rated Wire: Best of Both Worlds

THHN/THWN-2 wire is rated 90°C in dry locations AND 90°C in wet locations. This makes it suitable for virtually any building wire application. Most major manufacturers produce their building wire this way.

When you buy "THHN" from a supply house today, you're almost certainly getting THHN/THWN-2 dual-rated wire. But always verify by checking the markings on the wire itself.

What is a "Wet Location"?

Per NEC Article 100 definitions:

Wet Locations Include:

  • Underground installations
  • Concrete slabs in direct contact with earth
  • Locations subject to saturation with water
  • Unprotected outdoor locations
  • Below-grade conduit (even if above water table)

Damp Locations Include:

  • Protected outdoor locations (under canopies)
  • Interior locations subject to moderate moisture
  • Some basements

Important: Any conduit run underground, through a slab, or outdoors is considered a wet location - even if the conduit appears dry. Always use wet-rated wire in these applications.

Temperature Rating and Ampacity

The wire's temperature rating affects its ampacity from NEC Table 310.16:

Wire Size75°C Column90°C Column
12 AWG25A30A
10 AWG35A40A
8 AWG50A55A
6 AWG65A75A

Remember the Termination Rule

Even with 90°C wire, you typically use the 75°C ampacity column because most terminations (breakers, devices) are rated 75°C. The 90°C rating is mainly useful for derating calculations.

When to Use What

Use THHN/THWN-2 (Dual-Rated) For:

  • All general conduit work
  • Underground conduit runs
  • Outdoor conduit
  • Anywhere you need flexibility for future changes

Other Wire Types to Know:

  • XHHW-2 - Cross-linked polyethylene, excellent for wet locations
  • USE-2 - Underground service entrance (direct burial rated)
  • NM-B - Romex, for dry indoor locations only
  • UF-B - Underground feeder, direct burial rated

Bottom Line

For most electricians doing conduit work:

  1. Buy THHN/THWN-2 dual-rated wire (most common at supply houses)
  2. Verify the wire jacket shows both ratings
  3. You'll be covered for both dry and wet locations
  4. Use the 90°C rating for derating calculations, 75°C for final ampacity

Size Wire Correctly Every Time

Ampora's wire sizing calculator handles temperature ratings, derating factors, and NEC ampacity tables automatically.

Related Articles