NEC Article 240 Explained: Complete Guide to Overcurrent Protection
Master the requirements for fuses, circuit breakers, conductor protection, and tap rules. Essential knowledge for every electrician.
What is Overcurrent Protection?
Overcurrent protection is the backbone of electrical safety. NEC Article 240 covers the requirements for overcurrent protective devices (OCPDs) including fuses and circuit breakers. These devices protect conductors and equipment from damage caused by overcurrent conditions—whether from overloads or short circuits.
Without proper overcurrent protection, conductors can overheat, insulation can fail, and fires can result. Understanding Article 240 is essential for sizing breakers correctly and ensuring safe installations.
Standard Ampere Ratings (240.6)
The NEC specifies standard ampere ratings for fuses and fixed-trip circuit breakers. You must use these standard sizes:
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000
For circuits 800A and below, if the conductor ampacity doesn't match a standard rating, you may use the next higher standard rating—but only if certain conditions are met per 240.4(B).
Conductor Protection (240.4)
The fundamental rule: Conductors must be protected at their ampacity. The OCPD rating cannot exceed the conductor's ampacity as determined by NEC Table 310.16.
Small Conductor Rules (240.4(D))
For small conductors, specific maximum OCPD ratings apply:
| Conductor Size | Maximum OCPD |
|---|---|
| #14 AWG Copper | 15 Amperes |
| #12 AWG Copper | 20 Amperes |
| #10 AWG Copper | 30 Amperes |
Tap Rules (240.21)
Tap conductors are an exception to the general rule that OCPDs must be at the point where conductors receive their supply. The NEC allows taps under specific conditions.
10-Foot Tap Rule (240.21(B)(1))
The most commonly used tap rule allows conductors up to 10 feet without overcurrent protection at the tap point:
10-Foot Tap Requirements:
- Tap length ≤ 10 feet
- Tap ampacity ≥ 10% of feeder OCPD rating
- Tap ampacity ≥ combined calculated loads
- Tap does not extend beyond the equipment it supplies
- Tap is enclosed in raceway (except at point of termination)
- Tap terminates in a single OCPD that limits current to tap ampacity
25-Foot Tap Rule (240.21(B)(2))
For longer taps in installations with higher voltage or larger feeders:
- Tap length ≤ 25 feet
- Tap ampacity ≥ 1/3 of feeder OCPD rating
- Tap terminates in a single OCPD
- Tap is protected from physical damage
Circuit Breaker vs. Fuse
Both serve the same purpose but operate differently:
Circuit Breakers
- • Resettable after tripping
- • Higher initial cost
- • Easier to operate
- • May wear over time
- • Standard in most panels
Fuses
- • Must be replaced after operation
- • Lower initial cost
- • Faster response to faults
- • No mechanical wear
- • Common in industrial settings
Ground-Fault Protection of Equipment (240.13)
For solidly grounded wye electrical services of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase, with each disconnect rated 1000 amperes or more, ground-fault protection of equipment (GFPE) is required.
This is different from GFCI protection—GFPE protects equipment from ground faults, while GFCI protects people from shock hazards.
Common Mistakes to Avoid
Watch Out For:
- Oversizing breakers: Never upsize a breaker to stop nuisance tripping—find the cause instead
- Ignoring temperature ratings: Ampacity depends on conductor temperature rating and terminal ratings
- Improper tap applications: Verify all tap rule conditions are met
- Mismatched breakers: Only use breakers listed for your panel
Quick Reference: OCPD Sizing Steps
- 1. Calculate the load current
- 2. Size conductors per NEC Table 310.16 (with corrections)
- 3. Select OCPD ≤ conductor ampacity
- 4. Verify OCPD rating is a standard size per 240.6
- 5. Check for any special requirements (motors, A/C, etc.)
Use Ampora for Quick Calculations
Sizing overcurrent protection correctly requires considering multiple factors. The Ampora app helps electricians quickly determine proper OCPD ratings based on conductor size, load type, and installation conditions—all with NEC code references at your fingertips.
Get Overcurrent Protection Calculations Instantly
Download Ampora for wire sizing, breaker sizing, and NEC code reference on the job site.
Download Free on App Store