Calculations10 min readJanuary 10, 2025

How to Calculate Voltage Drop: Step-by-Step Guide for Electricians

Master voltage drop calculations for any circuit. Learn when to upsize conductors, understand NEC recommendations, and avoid inspection issues on long wire runs.

120VSOURCEDistance (D) = 150 ft108VAT LOADVD = 12V (10%)#12 AWG Copper

Need quick results?

Use our free voltage drop calculator for instant NEC-compliant calculations.

Open Calculator

What is Voltage Drop?

Voltage drop is the reduction in voltage that occurs as electrical current flows through a conductor due to the conductor's resistance. All conductors have some resistance, and when current flows through this resistance, some voltage is "lost" as heat according to Ohm's Law (V = I × R).

Excessive voltage drop causes:

  • Reduced equipment efficiency - Motors run hotter and less efficiently
  • Dimming lights - Especially noticeable with long lighting circuits
  • Equipment damage - Some equipment won't operate correctly at low voltage
  • Overheating conductors - Wasted energy turns to heat in the wire
  • Failed inspections - Inspectors may reject installations with excessive voltage drop

NEC Voltage Drop Requirements

The NEC provides voltage drop recommendations in NEC 210.19(A) Informational Note No. 4 and NEC 215.2(A)(4) Informational Note No. 2:

3%

Maximum recommended voltage drop for branch circuits

5%

Maximum recommended total voltage drop (feeder + branch circuit combined)

Important: These are recommendations, not requirements. However, many AHJs (Authority Having Jurisdiction) enforce these as requirements. Always check local codes and practices.

For a 120V circuit, 3% voltage drop equals 3.6V. For a 240V circuit, 3% equals 7.2V. For 480V three-phase, 3% equals 14.4V.

Voltage Drop Formulas

The standard voltage drop formula uses the conductor's resistivity, length, and circular mil area:

Single-Phase Formula

VD = (2 × K × I × D) / CM

Use for single-phase and DC circuits

Three-Phase Formula

VD = (1.732 × K × I × D) / CM

Use for three-phase circuits (√3 = 1.732)

Variable Definitions

  • VD = Voltage drop (volts)
  • K = Resistivity constant: 12.9 for copper, 21.2 for aluminum
  • I = Current (amps)
  • D = One-way distance (feet) - not round trip!
  • CM = Circular mils of the conductor (from NEC Chapter 9 Table 8)

To calculate voltage drop percentage:

VD% = (VD / Source Voltage) × 100

Single-Phase Calculation Example

Problem:

Calculate the voltage drop for a 120V, 20A circuit using 12 AWG copper wire with a one-way distance of 150 feet.

Step 1: Identify values

K = 12.9 (copper), I = 20A, D = 150 ft, CM = 6530 (12 AWG)

Step 2: Apply single-phase formula

VD = (2 × 12.9 × 20 × 150) / 6530

Step 3: Calculate

VD = 77,400 / 6530 = 11.86 volts

Step 4: Convert to percentage

VD% = (11.86 / 120) × 100 = 9.88%

Result: FAILS 3% Rule

At 9.88% voltage drop, this circuit exceeds the 3% NEC recommendation. The conductor needs to be upsized to reduce voltage drop.

Solution: Upsizing to 6 AWG (26240 CM) would give: VD = 77,400 / 26240 = 2.95V (2.46%) ✓

Three-Phase Calculation Example

Problem:

Calculate the voltage drop for a 480V three-phase, 100A circuit using 1 AWG copper wire with a one-way distance of 200 feet.

Step 1: Identify values

K = 12.9 (copper), I = 100A, D = 200 ft, CM = 83690 (1 AWG)

Step 2: Apply three-phase formula

VD = (1.732 × 12.9 × 100 × 200) / 83690

Step 3: Calculate

VD = 446,856 / 83690 = 5.34 volts

Step 4: Convert to percentage

VD% = (5.34 / 480) × 100 = 1.11%

Result: PASSES 3% Rule

At 1.11% voltage drop, this circuit is well within the 3% NEC recommendation.

Wire Gauge Circular Mils Table

Reference table for common wire gauges (from NEC Chapter 9, Table 8):

AWG/kcmilCircular Mils (CM)Typical Use
14 AWG411015A lighting circuits
12 AWG653020A receptacle circuits
10 AWG1038030A circuits, dryers
8 AWG1651040A circuits, ranges
6 AWG2624050-55A circuits
4 AWG4174065-70A circuits
2 AWG6636090-95A circuits
1 AWG83690110A circuits
1/0 AWG105600125A circuits
2/0 AWG133100145A circuits
3/0 AWG167800165A circuits
4/0 AWG211600195A circuits

When to Upsize Conductors

You should consider upsizing conductors for voltage drop when:

  • Wire runs exceed 100 feet
  • Calculated voltage drop exceeds 3% on branch circuits
  • Total feeder + branch circuit drop exceeds 5%
  • Sensitive electronic equipment is being powered
  • Motor loads require full starting voltage
  • LED lighting circuits (LEDs are sensitive to voltage variations)

Pro Tip: The 100-Foot Rule of Thumb

For quick field estimates: If your wire run exceeds 100 feet at full circuit load, you likely need to upsize. Always verify with calculation, but this rule catches most voltage drop issues before they become inspection problems.

Calculate Voltage Drop Instantly

Skip the manual calculations. Ampora's voltage drop calculator handles single-phase and three-phase circuits automatically, with NEC-compliant recommendations.

Related Articles